The electrical load characteristics are basic information needed by Electrical Consultant, when designing an electrical system for a refinery. In establishing such data like load density, demand factor and load factor, it was necessary to conduct a research so as to ascertain the parameters in an existing industry, where Warri refinery was taken as a case study. The research came out with the following useful data for: Load density = 12.8 VA M 2, Load factor = 88.5%, Demand factor = 24.4%.
F.O. Usifo , Oria-Usifo Eromosele and B.S.O. Ighalo . Investigation of Electrical Load Characteristics at Warri Refinery and Petrochemical Ltd., Warri.
DOI: https://doi.org/10.36478/rjasci.2007.1261.1265
URL: https://www.makhillpublications.co/view-article/1815-932x/rjasci.2007.1261.1265