@article{MAKHILLRJAS20072128877, title = {Investigation of Electrical Load Characteristics at Warri Refinery and Petrochemical Ltd., Warri}, journal = {Research Journal of Applied Sciences}, volume = {2}, number = {12}, pages = {1261-1265}, year = {2007}, issn = {1815-932x}, doi = {rjasci.2007.1261.1265}, url = {https://makhillpublications.co/view-article.php?issn=1815-932x&doi=rjasci.2007.1261.1265}, author = {F.O. Usifo,Oria-Usifo Eromosele and}, keywords = {Load characteristics,electrical consultant,refinery,demand factor,load factor}, abstract = {The electrical load characteristics are basic information needed by Electrical Consultant, when designing an electrical system for a refinery. In establishing such data like load density, demand factor and load factor, it was necessary to conduct a research so as to ascertain the parameters in an existing industry, where Warri refinery was taken as a case study. The research came out with the following useful data for: Load density = 12.8 VA M 2, Load factor = 88.5%, Demand factor = 24.4%.} }