TY  - JOUR
T1  - Investigation and Evaluation of Voltage Drops: A Case Study of Guinness and Ikpoba Dam Injection Substations
AU - , M.S. Okundamiya AU - , O.S. Udeozor AU - , O.J. Imade 
JO  - International Journal of Electrical and Power Engineering
VL  - 3
IS  - 2
SP  - 105
EP  - 111
PY  - 2009
DA  - 2001/08/19
SN  - 1990-7958
DO  - ijepe.2009.105.111
UR  - https://makhillpublications.co/view-article.php?doi=ijepe.2009.105.111
KW  - Voltage drops
KW  -substation
KW  -injection substation
KW  -consumers load distance
KW  -power distribution
AB  - This study presents an in-depth analysis and evaluation of the amount of voltage drops in houses along selected streets in Benin city, which was restricted to Power Holding Company of Nigeria (PHCN). The study embraced the readings of the transformer supplied voltage, house-to-house received voltage, currents, power consumption in each house using clip-on metre, while the distance of each house from the transformer supplying, the street was obtained using measuring tape. The results obtained shows that if consumers are to receive a reasonable supplied voltage for efficient operation of their appliances the distance of the consumerâ€™s service cable at the farthest end from the transformer should not exceed 400 m.
ER  - 