TY  - JOUR
T1  - A Fire Protection System with Thermo-Sensitive Tube by One
Cylinder for Two Switchboards
AU - Jin, Kyung-Jin AU - Kong, Ha-Sung 
JO  - Journal of Engineering and Applied Sciences
VL  - 12
IS  - 5
SP  - 1092
EP  - 1096
PY  - 2017
DA  - 2001/08/19
SN  - 1816-949x
DO  - jeasci.2017.1092.1096
UR  - https://makhillpublications.co/view-article.php?doi=jeasci.2017.1092.1096
KW  - cylinder
KW  -selector valve
KW  -fire protection
KW  -Thermo-sensitive tube
KW  -switchboard
KW  -cylinder
KW  -selector valve
KW  -fire protection
AB  - The purpose of this research is to increase economic efficiency by adapting a selector valve to a
switchboard to protect two switchboards with one cylinder. As a result of the detection tube&#146;s operating
temperature test, it was confirmed that the thermo-sensitive tube operates within &plusmn;5%. In the dispersion
performance test, the switchboard fire protection system using selector valve detected fire within 5 sec on
average and dispersed fire-extinguishing agent immediately. The fire-extinguishing agent&#146;s dispersion time was
about 47 sec and was suitable for the dispersion performance test&#146;s acceptance criteria of the dispersion within
60 sec. Through this experiment, it was found that the thermo-sensitive tube used in the experiment was suitable
for the acceptance criteria. It was also found that it was effective to protect two switchboards with one cylinder
unlike the conventional case.
ER  - 