AB  - In this study, high efficient power conditioner system for 
  grid integrated variable-speed wind turbine using an Interior Permanent-Magnet 
  Synchronous Generator (IPMSG) is developed. The grid integrated Power Conditioner 
  System (PCS) consists of phase-shifting transformer which powers series-type 
  12-pulse uncontrolled diode rectifier which is cascaded to a Pulse Width Modulated 
  (PWM) diode clamped multilevel inverter. The active current of the grid-side 
  PWM multi level inverter is controlled to follow the optimal active current 
  reference. In proposed system the passive filter together with a series-type 
  12-pulse rectifier suppresses the distortions presented in the IPMSG voltages 
  and currents and increases the efficiency by compensating the power factor angle 
  of the IPMSG. Simulation results proves that the proposed reduces the harmonics 
  and it is high efficient.