TY  - JOUR
T1  - Investigation of Electrical Load Characteristics at Warri Refinery and Petrochemical Ltd., Warri
AU - , F.O. Usifo AU - , Oria-Usifo Eromosele AU - , B.S.O. Ighalo 
JO  - Research Journal of Applied Sciences
VL  - 2
IS  - 12
SP  - 1261
EP  - 1265
PY  - 2007
DA  - 2001/08/19
SN  - 1815-932x
DO  - rjasci.2007.1261.1265
UR  - https://makhillpublications.co/view-article.php?doi=rjasci.2007.1261.1265
KW  - Load characteristics
KW  -electrical consultant
KW  -refinery
KW  -demand factor
KW  -load factor
AB  - The electrical load characteristics are basic information needed by Electrical Consultant, when designing an electrical system for a refinery. In establishing such data like load density, demand factor and load factor, it was necessary to conduct a research so as to ascertain the parameters in an existing industry, where Warri refinery was taken as a case study. The  research came out with the following useful data for: Load density = 12.8 VA M <SUP>2</SUP>, Load factor = 88.5%, Demand factor = 24.4%.
ER  - 