TY  - JOUR
T1  - A Novel Scheme to Extract Incident Voltage Traveling-Waves of EHV Transmission Lines
AU - , Zhihua-Wang AU - , Xianggen-Yin AU - , Deshu-Chen AU - , Xiaobo-Zhang AU - , Jingchao-Yang 
JO  - Asian Journal of Information Technology
VL  - 3
IS  - 10
SP  - 890
EP  - 897
PY  - 2004
DA  - 2001/08/19
SN  - 1682-3915
DO  - ajit.2004.890.897
UR  - https://makhillpublications.co/view-article.php?doi=ajit.2004.890.897
KW  - 
AB  - CVTs with passive ferro-resonance circuits have flat high-frequency characteristics which cover the frequency band from 10kHz to several hundreds kHz, the secondary voltages are directly used to extract voltage incident traveling-waves without the need of specially designed voltage traveling-wave transducers. And wavelet transform modulus sum based arrival detection of incident traveling-wave is proposed, simulation and experiment data are given to verify the schemes, which will be useful in applications of fault location and relay protection using incident voltage traveling-waves.
ER  - 